SAE TERM 100

saetrattamentoacqua-prodotti-chimici-SAE TERM 100

Multifunctional additive specifically formulated for water conditioning
closed heating and/or cooling circuits.
Effectively inhibits the formation of corrosion on steels, copper, copper alloys, alloys
of aluminium, in circuits replenished with hard, softened or osmotic water; his action
it is not inhibited if glycol is present in the circuit as an antifreeze.
Prevents the formation of deposits due to the precipitation of hardness salts.

1 kg bottle
10 kg tank
25 kg tank

Instructions for Use

Clean the heating systems with SAE TERM 300 as required by the UNI 8065 standard. Check or calculate the water content of the system. Fill the heating system halfway with water. Introduce the necessary quantity of protective agent using a loading pump. Fill the system with water, vent it well and turn on the pumps to circulate the water. After about an hour, check the product concentration with the MOLYBDENUM KIT, the concentration must be 140mg/L. Recheck the product concentration after 1 to 3 months and refill the system with water and protective liquid. In case of a dosage lower than 140mg/L the protection will not be effective and corrosion and sludge formation may occur again. Check the dosage every 2 years as per the UNI standard.

Mixture proportions

1% (1 liter SAE TERM 100 per 100 liters of heating water). Attention, the product must not be over or under dosed.

Documentation

Scheda tecnica